shenzhen kylcom communication equipment co., ltd.rf models rf io models-金沙js1005线路

kyl-812

features

 

4-way i/o module can achieve wireless transmission in real time,the relay output of receiver module is connceting with on-off input of the transmitter relay output.in other words,when the input of the transmitter switch on,the corespond relay output will be on at the same time.when the input of the transmitter switch off,the corespond relay output will be off at the same time.all channels are independent.no program,no wires,users can remote control switching.this product is widely-used in industrial controller,wireless monitoring,waterworks automation and other projects. 


一、kyl-812 application diagram

80204.jpg

二、kyl-802 connection diagram

        80205.jpg




 

application

 

wireless water pump automatic control

       wireless sound and light alarm lights

       industrial remote control, industrial site monitoring

       wireless car control

       water plant automation

       traffic automation control

       environmental monitoring system

       oil pipeline monitoring system

 

technical specification 
                                                                   
                                                                kyl-812 parameters

featuresrangetypical valueremark
power supply d.c.9-15v12voutput current≥500ma
transmission distance1-3km- line-of-sight
ourput no. -4 output-
output type-relaymaximum load capacity dc   220v5a
input no. -4 input-
input type i-dry contact-
input type iidc   0-24vlow level<1vlow level corresponds to closed
high level>4.5vhigh level corresponding to disconnected
transmitting current -<300ma-
receiving current-<20ma-
dimension-82mm*82mm-

remarks: the input type has been specified according to the customer's requirements. so can not be changed after shipment.


 kyl-812 terminals and hardware introduction

               80206.jpg

 the function-indicator light

1、power indicator-pwr:power on

2、data indicator-t/r:flashes once per second, indicating that the module is operating normally

3、running lights-run:the indicator flashes when the module transmits/receives data each time

4-7:switch output status indication d1-d4:the indicator light is on, indicating that the corresponding output channel is closed, otherwise it is disconnected

dip switch definitions
1、
 dip1-4:channels choosing

blob.png

2、dip5-8:working mode choosing  

blob.png

remark:

    *users generally use the inputting change sending mode, dip7-on;

    *to avoid more than two remote control systems working at the same time in one remote control range, the        module for different system should choose different channel (working frequency);

    *in timing mode, one must be the master and the other is the slave

    *it should be effect by re-power on the module after changing the dip position.



pin definitions

 

connection namepin no.definition remarks 
com11gndgrounding of power supply
2vccdc:9-15v
com21in1first group on-off input
2gnd
3in2second group on-off input
4gnd
5in3third group on-off input
6gnd
7in4fourth group on-off input
8gnd
com31led1first channel voltage controlling output (5v)
2gnd
3led2second channel voltage controlling output(5v)
4gnd
5led3third channel voltage controlling output(5v)
6gnd
7led4fourth channel voltage controlling output (5v)
8gnd
com41out1first channel relay dry contact output
2gnd
3out2second channel relay dry contact output
4gnd
5out3third channel relay dry contact output
6gnd
7out4fourth channel relay dry contact output
8gnd

using method 

 

1、install the antenna to the module.

    2, in accordance with the use of demand, according to the above instructions set the dip switch, connect          the corresponding switch input, switch output device.

    3, connect the power (12-30v), turn on the power switch, the power requirements of the output current needs        reach more than 500ma.

    4, at this point, the input of module can control the output of another module .

    5, the module is two-way transmission, that is, a module can as an input ,at the same time, can also be            used as a controlled output, and vice versa.

    6, within the same remote control distance range if user using more than two sets of remote control system,        one should use a different operating frequency to avoid mutual interference.





working mode

 

1、triger mode

       when on-off input status changed,it will triger i/o module to send the local status information. this          mode has fast speed,can be in real time.only when input status changed,then will send the signal,the            energy consumption will be low. 

   2、timer mode

      at this mode, there should be one master and one slave module. the master will

      synchronize with the slave every 1s, means the master will transmits its condition to slave every 1s and       the slave will feedback its condition to master every 1s. if the time master cannot synchronize with           slave reaches at 3s, all contacts will disconnect. they connects until the master is synchronizing with         slave again. there will be 1s transmission delay at this mode.

   3、collecting mode

      at collecting mode, dip8(transmitting mode), dip7(master/slave mode) and dip5(repeater/feedback mode) are       all invalid. at this mode, module works as a modbus slave, it can not transmit data actively. master can       be a pc connecting with a wireless data module or other data terminal. data terminal sends modbus rtu

      command and requests slave feedback collection condition or control slave’s on-off output. slave’s id         can be 1 to 254.

  4、feedback/repeater mode

     at feedback/repeater mode, receiver will retransmit the command it received and make it reach longer            distance. it functions as a repeater. the transmitter will output related on-off condition on its output        com after receiving retransmitted command, meanwhile, the output indicator will be on/off. its output          condition will be the same with its input condition. if receiver didn’t receive the command, it will not      retransmit, feedback will fail. master’s output condition will be not the same with its input. this            function can monitor receiver’s output results.if the user is not familiar with the product and is            unfamiliar with the method of use, all code switches should be pull to the on position to test.



 

kyl-812 other application

 

kyl-812 can work with same series i/o module: kyl-813 or kyl-818 etc,to reach the function of centralized control,and centralized output (please indicate to sales when you set the purchase order).please look the below diagram as example:

80209.jpg

ordering information

standard products

module nameremark 
 kyl-812ubi-directional, 2pcs of this rf modules will help you do wireless communication., no program, plastic housing, communication distance 600m-1km (line of sight) based on power 100mw
 kyl-812bi-directional, 2pcs of this rf modules will help you do wireless communication., no program, plastic housing, communication distance 2km-3km (line of sight) based on power 800mw
packaging accessories

1、standard accessories

1、1pc kyl-812 module。

        2、1pc antenna

        pic.:standard accessories 




80210.jpg

2、selectable accessories

1、selectable antenna。(users can choose antenna if need)

        pic.:selectable accessories



80211.jpg






 

previous: 485 test line
next: kyl-668h
网站地图